Siemens Simatic 6ES7214-1HG31-0XB0 (6ES7214-1HG31-0XB0)

Siemens Simatic 6ES7214-1HG31-0XB0
Siemens Производитель: Siemens
27 574 р.
Наличие: уточняйте
Минимальный заказ: 5000 руб.

Минимальный заказ: 5000 руб.

Тендеры

Принимаем участие и помогаем нашим клиентам выигрывать тендеры и поставлять требуемую продукцию!

Гарантия

На всё сетевое и серверное оборудование предоставляется гарантия до 3-х лет, в том числе на снятые с производства позиции.

Описание Siemens Simatic 6ES7214-1HG31-0XB0

SIMATIC S7-1200, CPU 1214C,COMPACT CPU, DC/DC/RELAY,ONBOARD I/O: 14 DI 24V DC;10 DO RELAY 2A;2 AI 0 - 10V DC,POWER SUPPLY: AC 20.4 - 28.8 V DC,PROGRAM/DATA MEMORY: 75 KB
General information
Engineering with
Programming package
STEP 7 V11 SP2 or higher
Supply voltage
24 V DC
Yes
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Load voltage L+
Rated value (DC)
24 V
permissible range, lower limit (DC)
5 V
permissible range, upper limit (DC)
250 V
Input current
Current consumption (rated value)
500 mA ; Typical
Current consumption, max.
1.2 A ; 24 V DC
Inrush current, max.
12 A ; at 28.8 V
Encoder supply
24 V encoder supply
24 V
Permissible range: 20.4V to 28.8V
Output current
Output current Current output to backplane bus (5 V DC), max.
1600 mA ; Max. 5 V DC for SM and CM
Power loss
Power loss, typ.
12 W
Memory
Type of memory
EEPROM
usable memory for user data
75 kbyte
Work memory
integrated
75 kbyte
expandable
No
Load memory
integrated
4 Mbyte
Backup
present
Yes ; maintenance-free
without battery
Yes
CPU processing times
for bit operations, typ.
0.085 µs ; / instruction
for word operations, typ.
1.7 µs ; / instruction
for floating point arithmetic, typ
2.5 µs ; / instruction
CPU-blocks
Number of blocks (total)
DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
Number, max
Limited only by RAM for code
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max.
10 kbyte
Flag
Number, max.
8 kbyte ; Size of bit memory address area
Address area
I/O address area
I/O address area, overall
1024 bytes for inputs / 1024 bytes for outputs
Process image
Inputs, adjustable
1 kbyte
Outputs, adjustable
1 kbyte
Hardware configuration
Number of modules per system, max.
3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
Hardware clock (real-time clock)
Yes
Deviation per day, max.
60 s/month at 25 °C
Backup time
480 h ; Typical
Digital inputs
Number of digital inputs
14 ; Integrated
of which inputs usable for technological functions
6 ; HSC (High Speed Counting)
integrated channels (DI)
14
m/p-reading
Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max14
Input voltage
Rated value, DC 24 V
for signal "0" 5 V DC at 1 mA
for signal "1" 15 VDC at 2.5 mA
Input current
for signal "1", typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
parameterizable 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
at "0" to "1", min. 0.2 ms
at "0" to "1", max 12.8 ms
for interrupt inputs
parameterizable Yes
for counter/technological functions
parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz
Cable length
Cable length, shielded, max. 500 m ; 50 m for technological functions
Cable length unshielded, max. 300 m ; For technological functions: No
Digital outputs
Number of digital outputs 10 ; Relays
integrated channels (DO) 10
Short-circuit protection No ; to be provided externally
Switching capacity of the outputs
with resistive load, max. 2 A
on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
"0" to "1", max. 10 ms ; max.
"1" to "0", max. 10 ms ; max.
Switching frequency
of the pulse outputs, with resistive load, max. 1 Hz
Relay outputs
Max. number of relay outputs, integrated 10
Number of relay outputs 10
Number of operating cycles, max mechanically 10 million, at rated load voltage 100,000
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Analog inputs
integrated channels (AI) 2 ; 0 to 10 V
Number of analog inputs 2
Input ranges
Voltage Yes
Input ranges (rated values), voltages
0 to +10 V Yes
Input resistance (0 to 10 V) ?100k ohms
Cable length
Cable length, shielded, max. 100 m ; twisted and shielded
Analog outputs
Number of analog outputs 0
Analog value generation
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max. 10 bit
Integration time, parameterizable Yes
Conversion time (per channel) 625 µs
Encoder
Connectable encoders
2-wire sensor Yes
1. Interface
Interface type PROFINET
Physics Ethernet
isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
PROFINET IO Controller Yes
Communication functions
S7 communication
supported Yes
as server Yes
as client Yes
Open IE communication
TCP/IP Yes
ISO-on-TCP (RFC1006) Yes
UDP Yes
Web server
supported Yes
User-defined websites Yes
Test commissioning functions
Status/control
Status/control variable Yes
Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
Forcing Yes
Diagnostic buffer
present Yes
Integrated Functions
Number of counters 6
Counting frequency (counter) max. 100 kHz
Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Galvanic isolation
Galvanic isolation digital inputs
Galvanic isolation digital inputs 500V AC for 1 minute
between the channels, in groups of 1
Galvanic isolation digital outputs
Galvanic isolation digital outputs Relays
between the channels No
Permissible potential difference
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes
Test voltage at air discharge 8 kV
Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
on the supply lines acc. to IEC 61000-4-4 Yes
Interference immunity on signal cables acc. to IEC 61000-4-4 Yes
Interference immunity against voltage surge
on the supply lines acc. to IEC 61000-4-5 Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes
Emission of radio interference acc. to EN 55 011
Emission of radio interference acc. to EN 55 011 (limit class A) Yes ; Group 1
Emission of radio interference acc. to EN 55 011 (limit class B) Yes ; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
RCM (former C-TICK) Yes
FM approval Yes
Marine approval
Marine approval Yes
Ambient conditions
Operating temperature
min. -20 °C
max. 60 °C
horizontal installation, min. -20 °C
horizontal installation, max. 60 °C
vertical installation, min.-20 °C
vertical installation, max. 50 °C
min. -40 °C
max. 70 °C
Air pressure
Operation, min. 795 hPa
Operation, max 1080 hPa
Storage/transport, min. 660 hPa
Storage/transport, max 1080 hPa
Relative humidity
Operation, max 95 % ; no condensation
Vibrations
Vibrations 2G wall mounting, 1G DIN rail
Operation, tested according to IEC 60068-2-6 Yes
Shock test
tested according to IEC 60068-2-27 Yes ; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Dimensions
Width 110 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 435 g

27 574 р.